Item/Type
|
|
Horizontal Fire Tube Automatic Oil/Gas Fired Steam Boiler
|
|
|
|
|
|
|
|
||||||||
Rated capacity t/h
|
|
3
|
4
|
5
|
6
|
8
|
10
|
15
|
20
|
||||||||
Rated steam pressure MPa
|
|
0.7/1.0/1.25/1.6
|
|
|
|
|
|
|
|
||||||||
Rated steam temperature ℃
|
|
170/184/194/204
|
|
|
|
|
|
|
|
||||||||
Boiler thermal efficiency %
|
|
92.55
|
92.6
|
92.5
|
92.9
|
93.1
|
93.4
|
93.5
|
93.7
|
||||||||
Body heating area m2
|
Boiler body
|
67.87
|
80.37
|
110.5
|
140.13
|
194.27
|
142.3
|
218.5
|
275.3
|
||||||||
|
Economizer
|
30.4
|
43.41
|
46.5
|
57.1
|
74.4
|
112.6
|
155
|
225.5
|
||||||||
Boiler water volume m3
|
|
6.25
|
7.54
|
8.9
|
8.5
|
13.9
|
19.5
|
24.5
|
31.5
|
||||||||
Flue diameter mm
|
|
φ450
|
φ520
|
750x410
|
800x410
|
940x520
|
850x500
|
1200x600
|
1500x600
|
||||||||
Water inlet diameter DN
|
|
40
|
50
|
50
|
50
|
50
|
50
|
65
|
80
|
||||||||
Main steam valve diameter DN
|
|
100/40
|
100/40
|
125/40
|
125/40
|
150/40
|
150/40
|
200/50
|
200/65
|
||||||||
Safety valve diameter DN
|
|
2x40
|
50+40
|
2x50
|
2x65
|
2x65
|
2x80
|
2x100
|
2x100
|
||||||||
Blowdown diameter DN
|
|
40
|
40
|
40
|
40
|
40
|
2x50
|
2x50
|
2x50
|
||||||||
Fuel consumption
|
Diesel kg/h
|
177.65
|
236.74
|
296.25
|
353.97
|
470.95
|
586.79
|
879.25
|
1169.83
|
||||||||
|
Natural gas Nm³/h
|
217.25
|
289.51
|
362.28
|
432.40
|
573.44
|
717.57
|
1075.21
|
1430.55
|
||||||||
Largest transportation size
|
Length mm
|
4600
|
4900
|
5250
|
5850
|
6500
|
6240
|
8500
|
9200
|
||||||||
|
Width mm
|
2200
|
2300
|
2350
|
2400
|
2600
|
2850
|
3500
|
3950
|
||||||||
|
Height mm
|
2500
|
2650
|
2680
|
2700
|
2850
|
3100
|
4000
|
4350
|
||||||||
Largest transportation weight kg
|
|
8000
|
8700
|
11200
|
12500
|
17800
|
22000
|
32500
|
40500
|