Project
|
|
|
Specifications
|
||
Power input
|
Rated input voltage (V)
|
|
3-phase 380 V (-15%~+30%)
|
||
|
Rated input current (A)
|
|
See table 2-1
|
||
|
Rated input frequency(Hz)
|
|
50Hz/60Hz,tolerance±5%
|
||
Power output
|
Applicable motor(kW)
|
|
See table 2-1
|
||
|
Rated output current(A)
|
|
See table 2-1
|
||
|
The maximum output voltage(V)
|
|
0~rated input voltage, error<±3%
|
||
|
The maximum output frequency(Hz)
|
|
0.00~600.00 Hz,unit0.01Hz
|
||
Control
characteristics |
V/f patterns
|
|
V/f control
Sensor-less vector control 1 Sensor-less vector control 2 |
||
|
Speed range
|
|
1:50 (V/f control)
1:100 (sensor-less vector control 1) 1:200(sensor-less vector control 2) |
||
|
Speed accuracy
|
|
±0.5% (V/f control)
±0.2% (sensor-less vector control 1 & 2) |
||
|
Speed fluctuation
|
|
±0.3% (sensor-less vector control 1 & 2)
|
||
|
Torque response
|
|
< 10ms (sensor-less vector control 1 & 2)
|
||
|
Starting torque
|
|
0.5Hz: 180% (V/f control, sensor-less vector control 1)
0.25Hz: 180% (sensor-less vector control 2) |
||
Basic functions
|
Carrier frequency
|
|
0.7kHz~16kHz
|
||
|
Overload capability
|
|
G Model:150% Rated Current 60s,180% Rated Current 10s,200% Rated Current 1s.
P Model:120% Rated Current 60s,145% Rated Current 10s,160% Rated Current 1s. |
||
|
Torque boost
|
|
Automatic torque boost;Manual torque boost 0.1%~30.0%
|
||
|
V/F Curve
|
|
Three ways:Three ways: straight; multi-point type; N Th-type V / F curve(1.2 Th -type, 1.4 Th -type, 1.6 Th -type, 1.8 Th -type, 2
Th -type) |
||
|
Acceleration and deceleration Curve
|
|
Line or curve acceleration and deceleration mode.
Four kinds of acceleration and deceleration time,Ramp Time Range :0.0~6000.0s |
||
|
DC brake
|
|
DC brake start frequency: 0.00~600.00Hz
DC brake time:0.0s~10.0s DC brake current:0.0%~150.0% |
||
Basic functions
|
Jog brake
|
|
Jog frequency range:0.00Hz~50.00Hz.
Jog deceleration time: 0.0s~6000.0s. |
||
|
Simple PLC, Multi-speed
|
|
Through the built-in PLC or control terminal to achieve up to 16 speed running
|
||
|
Built-in PID
|
|
Facilitate the realization of process control loop control system
|
||
|
Automatic voltage adjustment(AVR)
|
|
When the grid voltage changes, can automatically maintain a constant output voltage
|
||
|
Fast current limit function
|
|
Minimize over current fault protection inverter running
|
||
|
Over voltage Over current
|
|
System automatically limits of current and voltage during operation to prevent frequent
|
||
Run
|
Command source
|
|
Given the control panel, control terminal, serial communication port given.
|
||
|
Frequency given
|
|
9 kinds of frequency given sources: digital setting, keyboard potentiometer setting, analog
Voltage, given analog current reference pulse is given, the serial port is given, multi-speed given, PLC is given, the process PI D reference. There are several ways to switch |
||
|
Input terminal
|
|
7 Switch input terminals, one way to make high-speed pulse input.
3-channel analog inputs, including 2-way 0~10V / 0~20mA voltage and current options, a way to support -10~+10 V input |
||
|
output
terminal |
|
2-way switch output terminal, which supports a maximum road speed 100kHz pulse output.
2 relay output terminals. 2 analog output terminal, and optional voltage and current. |
||
Featured
functions |
Parameter copy, parameter backup, flexible parameter displayed & hidden. Common DC bus(Contains below 30 KW).
Various master & auxiliary command and switchover. Reliable speed search started. A variety of Accel / Decel curves programmable. Timing control, fixed length control, count function. Three faults recorded. Over excitation brake, overvoltage stall protection programmable, under voltage stall protection programmable, restart upon power loss. Four kinds of Accel/Decel time. Motor thermal protection. Flexible fan control. Process PID control, simple PLC, 16-step speed control programmable. Wobble frequency control. Multi-functional key programmable, field-weakening control. High-precision torque control, V/f separated control, torque control at sensor-less vector control. |
|
|
||
Protection
function |
Provide fault protection dozen: Overcurrent, Overvoltage, Undervoltage, Overtemperature, Overload Etc Protection.
|
|
|
||
Display and keyboard
|
LED Display
|
Display Parameters
|
|
||
|
Key lock and function selection
|
Realize some or all of the keys locked, scope definition section keys to prevent misuse
|
|
||
|
Run and stop monitoring information
|
In the run or stop can be set to monitor U00 group four objects were.
|
|
||
Environment
|
Place of
operation |
Indoors, no direct sunlight, free from dust, corrosive gases,
flammable gases, oil mist, water vapor, water drop and salt, etc. |
|
||
|
Altitude
|
0~2000m
De-rate 1% for every 100m when the altitude is above 1000 meters |
|
||
|
Ambient
temperature |
-10℃~40℃
|
|
||
|
Relative
humidity |
5~95%, no condensation
|
|
||
|
Vibration
|
Less than 5.9m/s2 (0.6g)
|
|
||
|
Storage
temperature |
-20℃~+70℃
|
|
||
Others
|
Efficiency
|
Rated power≥93%
|
|
||
|
Installation
|
Wall-mounted or Flange mounting
|
|
||
|
IP grade
|
IP20
|
|
||
|
Cooling
method |
Fan cooled
|
|