I/O control with a program capacity of up to 256K steps and up to 655,36 points enables suitable system configuration ranging from small through to large scale. 1ms program scan and I/O refresh are possible. Function and performance distribution are possible in multi-CPU system configuration with up to 8 CPUs.
Both the hardware and software conform to the IEC 61131 international standard for programmable controllers.
Compatible with Ethernet, LonWorks, DeviceNet, PROFIBUS-DP, AS-i, and other diverse open networks.
Provides an environment in which each support tool can be launched by simply clicking on a device in a network structure diagram or system configuration diagram on a PC.
Allows setup of parameters of inverter and servo via SPH and enables remote data monitor operation, thereby eliminating troublesome wiring changes.
With the aid of an upgraded data processing function, mass memory storage, and a built-in Ethernet function, the SPH is capable of monitoring the operation of production systems and devices and recording operation history and errors in addition to conventional FA control, enabling you to use the controller for wider applications of IT-based remote monitoring, maintenance support, and preventive maintenance.
CPU and power supply redundancy can also be achieved in response to the growing demand for higher reliability.
Item | Specification | ||
---|---|---|---|
Physical environmental condition | Operating ambient temperature | 0 to 55°C | IEC 61131-2 |
Storage temperature | -25 to +70°C | ||
Relative humidity | 20 to 95%RH no condensation | ||
Pollution degree | 2 (Free from conductive dust) | ||
Corrosion immunity | Free from corrosive gases. Not stained with organic solvents | ||
Operating altitude | 2000m or less above sea level (Transport condition: 70kpa or more) | ||
Mechanical service condition | Vibration | Half amplitude: 0.15mm, Constant acceleration: 19.6m/s² two hours for each of three axes, total six hours. | |
Shock | Acceleration peak: 147m/s² three times for each of three axes | ||
Electrical service condition | Electrostatic discharge |
Contact discharge: ± 4kV
Aerial discharge: ± 8kV |
IEC 61000-4-2 |
Radiated, radio-frequency, electromagnetic field |
80 to 1000MHz (10V/m)
1.4~2.0GHz (3V/m) 2.0~2.7GHz (1V/m) |
IEC 61000-4-3 | |
EFT/B (Electrical fast transient/burst) |
Power supply line and I/O signal line (AC unshielded line): ±2 kV
Communication line and I/O signal line (DC, AC shielded line): ±1 kV |
IEC 61000-4-4 | |
Lightning impulse surge |
AC power supply: Common mode ±2 kV, normal mode: ±1 kV
DC power supply: Common mode ±0.5 kV, normal mode: ±0.5 kV |
IEC 61000-4-5 | |
Conducted radio frequency | 150kHz to 80MHz, 10V | IEC 61000-4-6 | |
Power frequency magnetic field | 50Hz, 30A/m | IEC 61000-4-8 | |
Square wave | ±1.5kV rise time 1ns, pulse width 1µs 50Hz | ||
Construction | Open Type device | ||
Cooling | Self-cooling |