Product Category
|
|
|
Automatic transfer switch
|
|
|
|
|||||
Product name
|
|
|
SQ5
|
|
|
|
|||||
Rated current In(A)
|
|
|
100A
|
160A
|
250A
|
630A
|
|||||
Rated insulation voltage Ui(V)
|
|
|
500
|
500
|
500
|
500
|
|||||
Medium strength(M)
|
|
|
3000
|
5000
|
5000
|
5000
|
|||||
Rated impulse withstand voltage Uimp kV
|
|
|
6
|
8
|
8
|
12
|
|||||
Rated working current (A)
|
400V
|
AC-31
|
100
|
160
|
250
|
630
|
|||||
|
|
AC-33
|
80
|
160
|
250
|
630
|
|||||
|
|
AC-35
|
100
|
160
|
250
|
536
|
|||||
|
200V
|
DC-31
|
100
|
160
|
250
|
630
|
|||||
|
|
DC-33
|
80
|
160
|
250
|
500
|
|||||
|
|
DC-35
|
100
|
125
|
200
|
500
|
|||||
Motor power (400V)KW
|
|
|
32
|
80
|
132
|
280
|
|||||
Rated breaking capacity (A Rms) AC33 380V
|
|
|
800
|
1000
|
1600
|
3200
|
|||||
Rated turn-on capability (A Rms) AC33 380V
|
|
|
1000
|
1250
|
2000
|
4000
|
|||||
Rated short-circuit capability Icm(kA peak)
|
|
|
8
|
12
|
17
|
30
|
|||||
Mechanical life(number of cycles)
|
|
|
6000
|
6000
|
4000
|
2000
|
|||||
Electrical
|
cosΦ=0.65 AC33
|
|
2000
|
1000
|
1000
|
500
|
|||||
transfer time
|
Ⅰ-0-Ⅱ or Ⅱ-0Ⅰ (S)
|
|
1.0
|
1
|
1.1
|
1.2
|
|||||
|
Ⅰ-0 or Ⅱ-o(S)
|
|
0.5
|
0.6
|
0.7
|
0.8
|
|||||
Electrical control energy consumption
|
24V(DC)(W)
|
|
25
|
75
|
75
|
90
|
|||||
|
220V(AC)(W)
|
|
25
|
75
|
75
|
90
|
|||||
Operating force distance(Nm)
|
|
|
12
|
19
|
26
|
39
|
|||||
Ambient temperature
|
|
|
The upper limit is +40C,the average value does not exceed+35C within 24 hours; the lower limit is-5C
|
|
|
|
|||||
altitude
|
|
|
The altitude of the installation site does not exceed 2000m
|
|
|
|
|||||
Installation Environment
|
|
|
No explosive atmosphere environment. No rain intrusion environment
|
|
|
|