CWX-15N DC5v DC12v ADC9-24V AC85-220V brass SS304 UPVC 2 way motorized ball valve
Data Sheet
Product model | CWX-15Q | CWX-15N |
Output torque | 1.5NM | 2NM |
Rated voltage |
DC3-6V
DC12V AC/DC9-24V AC220V AC85-265V |
DC3-6V
DC12V AC/DC9-24V AC220V AC85-265V |
Wiring Method |
CR01
CR02 CR02+ CR03 CR03A CR04 CR05 |
CR01
CR02 CR02+ CR03 CR03A CR03T CR04 CR05 |
Power | <3W | <2W |
Working current | Max100mA (CR04 except Max150mA) |
<100mA
(CR04 except Max150mA) |
Open/close time | <3s | 5S |
Position Indicator | yes (without by default) | yes (without by default) |
Manual override | No | No |
Gear Material | POM & metal gear | POM & metal gear |
Working pressure | Max1.0Mpa | Max1.0Mpa |
Valve Material |
Brass
UPVC Stainless Steel |
Brass
UPVC Stainless Steel |
Valve size | DN8-DN20 |
Max DN32
2way DN8-DN25 3Way DN8-DN25 Reduce Port DN25 or smaller |
Schematic & Dimension
Wiring Diagrams
CR01(two wires and reverse polarity )Voltage:DC3-6V/12V/24V
1.Connecting SW to OPEN , the valve opens , getting the position ,automatically power off, the valve remain fully open position
2.Connection SW to CLOSE , the valve close , getting the position ,automatically power off, the valve remains side passes position(fully closed)
CR02 (three wires two point control) Voltage:DC3-6V/12V/ 9-24V/AC24V/AC220V
1.Connecting SW to OPEN, the valve opens , getting the position ,automatically power off, the valve remain fully open position
2.Disconnecting SW to CLOSE, the valve close , getting the position and automatically power off, the valve remains fully close position
Note:AC24V/AC220V can only be used for CWX-50K series electric valves
CR03(three wires one point control)Voltage:DC3-6V/12V /ADC9-24V /AC220V
1.Connecting SW, the valve opens , getting the position ,automatically power off, thevalve remain fully open position
2.Disconnecting SW, the valve close , getting the position ,automatically power off, the valve remains side passes position (fully closed)
Note:When power is DC voltage and Red Wires is “+”,Blue wire is “-”
CR04(two wires and fail-safe/power-off return) Voltage:DC3-6V/ADC9-24V/AC220V
1.SW connecting ,the valve open, getting the position and the power off automatically,the valve remains fully open/close position
2.SW disconnecting ,the valve close, getting the position and power off automatically,the valve remains fully open/close position
CR05 (five wires micro controller with signal feedback) Voltage:DC3-6V/12V/24V
1.Connecting SW and OPEN , the valve opens , getting the position green wire output the OLS signal , the controller test the signal OLS, connect SW to STOP, the valve stops and remains fully open position
2.Connecting SW and CLOSE , the valve close , getting the position red wire output the CLS signal , the controller test the signal CLS, connect SW to STOP, the valve stops and remains fully close position,
Note:Please make sure the signal wires "red","black" and "green" be connected at first,then connect the power wires " yellow" and "blue"