QCX2 series magnetic starter is mainly applied to circuit of AC 50 or 60Hz,voltage up to 550Vfor far distance making and breaking circuit and frequently starting and controlling motor. It hasthe features of small volume, light weight, low power consumption, high efficiency, safe andreliable performance. It complies to IEC947-4-1. |
Specification |
Type |
Rated
Current(A) |
Maximum Power AC3 duty (KW) | SuitableThermal Relay(A) | |||||
220V
230V |
380V
400V |
415V | 440V | 500V |
660V
690V |
|||
QCX2-9 | 9 | 2.2 | 4 | 4 | 4 | 5.5 | 5.5 |
JR28 D1312
JR28 D1314 |
QCX2-12 | 12 | 3 | 5.5 | 5.5 | 5.5 | 7.5 | 7.5 | JR28 D1316 |
QCX2-18 | 18 | 4 | 7.5 | 9 | 9 | 10 | 10 | JR28 D1321 |
QCX2-25 | 25 | 5.5 | 11 | 11 | 11 | 15 | 15 |
JR28 D1322
JR28 D2353 |
QCX2-32 | 32 | 7.5 | 15 | 15 | 15 | 18.5 | 18.5 | JR28 D2355 |
QCX2-40 | 40 | 11 | 18.5 | 22 | 22 | 22 | 30 |
JR28 D3353
JR28 D3355 |
QCX2-50 | 50 | 15 | 22 | 25 | 30 | 30 | 33 |
JR28 D3357
JR28 D3359 |
QCX2-65 | 65 | 18.5 | 30 | 37 | 37 | 37 | 37 | JR28 D3361 |
QCX2-80 | 80 | 22 | 37 | 45 | 45 | 55 | 45 |
JR28 D3363
JR28 D3365 |
QCX2-95 | 95 | 25 | 45 | 45 | 45 | 55 | 45 | JR28 D3365 |
Dimension |