Model
|
|
GE33-20KVA
|
|
Rated capacity(KVA/KW)
|
|
20/16
|
|
Input specifications
|
|
|
|
Main circuit input
|
Rated input voltage (Vac)
|
380/400/415
|
|
|
Input voltage range (Vac)
|
±25%
|
|
|
Number of phases
|
Three phase five wire (3L+N+PE)
|
|
|
Input frequency range (Hz)
|
45~65
|
|
|
Input power factor
|
>0.95 (with filter)
|
|
|
Rated input voltage (Vac)
|
380/400/415
|
|
|
Input voltage range (Vac)
|
+10%,+15%,+20% (settable)- 10%, - 20%, - 30% (settable)
|
|
|
Number of phases
|
Three phase five wire (3L+N+PE)
|
|
|
Input frequency range (Hz)
|
± 2% (± 0.5%,+1%, ± 2%, ± 3% settable)
|
|
Output specification
|
|
|
|
Voltage (Vac)
|
|
380/400/415 ±1%
|
|
Output power factor
|
|
0.8
|
|
Frequency (Hz)
|
|
Automatic tracking bypass frequency
|
|
wave form
|
|
Sine wave THDV less than 1% (pure linear load)
|
|
Switching time (ms)
|
|
0
|
|
Overall efficiency
|
|
≥92%
|
|
Overload capacity
|
|
105%~110%: 60 min bypass; 110%~125%: 10 min bypass; 125% "150%: 1 min to bypass;>150%: 10 s to bypass
|
|
Battery
|
|
|
|
Battery voltage (Vac)
|
|
384
|
|
Environment
|
|
|
|
Operating temperature (° C)
|
|
-10~40
|
|
Storage temperature (° C)
|
|
-25 ^ 55 (without battery)
|
|
Relative humidity
|
|
0~95% (no frost)
|
|
Working altitude
|
|
<1500m,if it exceeds the limit,it shall be derated according to GB/T3859.2
|
|
Noise (dB)
|
|
<55(1m away from the equipment)
|
|
Other features
|
|
|
|
Caution function
|
|
Output overload, mains power abnormality, UPS fault, battery undervoltage, etc
|
|
Protection function
|
|
Output short circuit, overload, over temperature, battery undervoltage, output overvoltage and undervoltage, fan fault alarm
|
|
Communication function
|
|
Standard configuration: RS232/RS485 Optional: SNMP/JBUS/MODBUS/dry contact
|
|
Mechanical characteristics
|
|
|
|
Dimension (W * Hmm)
|
|
300*600*810
|
|
Net weight(kg)
|
|
150
|