100KW Weifang Series Gas Generator Set
|
|
|
|
|||
Unit model:
|
MG100GF
|
Steady state voltage adjustment rate (%):
|
≤± 1
|
|||
Output power:
|
100Kw
|
Voltage fluctuation rate (%):
|
≤ ± 0.5
|
|||
Power factor:
|
COSΦ = 0.8 (lagging)
|
Transient voltage adjustment rate (%):
|
+ 20 ~ -15
|
|||
Output voltage:
|
400V / 230V
|
Voltage stabilization time (s):
|
≤ 1
|
|||
Output current:
|
180A
|
Steady state frequency adjustment rate (%):
|
≤ ± 1
|
|||
Rated frequency:
|
50Hz
|
Frequency fluctuation rate (%):
|
≤ ± 0.5
|
|||
Rated speed:
|
1500rpm
|
Transient frequency adjustment rate (%):
|
+ 10 ~ -7
|
|||
Gas grade:
|
LNG/CNG
|
Frequency stabilization time (S):
|
≤3
|
|||
Dimensions:
|
2800×950× 1700 (L×W × H mm)
|
Gas consumption ( 100% load):
|
0.6L/kW · h
|
|||
Weight:
|
2200kg
|
Acoustic noise (LP7m):
|
≤95dB (A)
|
|||
Technical parameters of gas engine:
|
|
|
|
|||
Brand/origin:
|
Weifang Gas Engine
|
Cooling method:
|
closed water circulation cooling
|
|||
model:
|
6126ZLD-NG
|
Ignition method:
|
Spark plug ignition
|
|||
Number of cylinders / Dare to mention structure:
|
6 / L Type
|
control method:
|
ECU control
|
|||
Bore stroke:
|
126 × 130 mm
|
Intake method:
|
inhale naturally
|
|||
Compression ratio:
|
16.5 :1
|
Overload capacity:
|
110%
|
|||
Start mode:
|
DC 12V Electric start
|
Speed:
|
1500rpm
|
|||
Technical parameters of generator:
|
|
|
|
|||
Brand:
|
China Stanford
|
Protection level:
|
IP22
|
|||
Model:
|
LY- 100
|
W iring mode:
|
Three-phase four-wire, Y- connection
|
|||
Rated power:
|
100kW
|
Adjustment method:
|
AVR (Automatic Voltage Regulator)
|
|||
Rated voltage:
|
400V / 230V
|
Output frequency:
|
50Hz
|
|||
Insulation class:
|
H class
|
Output factor:
|
COSΦ = 0.8 (lag)
|
|||
The standard configuration of the generator set is as follows:
|
|
|
|
|||
Ø EFI internal combustion engine (gas);
|
|
|
|
|||
Ø AC synchronous generator (single bearing);
|
|
|
|
|||
ØSuitable for ambient temperature 40 C -50 C radiator water tank, belt driven cooling fan, fan safety shield;
|
|
|
|
|||
Ø Power generation output air switch, standard control screen;
|
|
|
|
|||
Ø Unit steel common base (including: unit vibration damping rubber pad);
|
|
|
|
|||
Ø Dry air filter, fuel oil, lubricating oil filter, start motor, and equipped with self-charging generator;
|
|
|
|
|||
Ø Random information: original technical documents of gas engine and generator, generator set manual, test report, etc.
|
|
|
|