Technical Specifications
|
|
|
Model
|
OR-AC380V-100KW-R Resistive AC Load Bank |
|
Load Element
|
Alloy resistors |
|
Load Voltage
|
AC380V 3 Phase 4 Wire AC220V single phase
|
|
Load Power
|
100KW for AC380V 3 Phase 4 Wire 34KW for AC220V single phase
|
|
Load Steps
|
Load steps for phaseA/B/C100W/200W/200W/500W/1KW/2KW/2KW/3KW/5KW/10KW/10KW
|
|
Power Factor
|
PF=1
|
|
Load Accuracy
|
±5%
|
|
Display
|
voltage, current, power, reactive power, energy, frequency, displayed by digital meter
|
|
Power Supply
|
220V(±10%) 50HZ, single phase |
|
Control Mode
|
Manual control by MCBs, push button switch
|
|
|
Remote control by PLC through PC software(optional)
|
|
Wire Connections
|
Internal terminal for wire connections (wires in/out down cabinet) |
|
Insulation Class
|
F
|
|
Protection Level
|
IP20(indoor use)
|
|
Fan Noise
|
75dB
|
|
Cooling Mode
|
Force-air cooling,
|
|
Work Mode
|
Continuous work
|
|
Protections
|
Overheating/Buzzer alarm, short circuit protection, phase sequence protection, Overheating/Over current & voltage protection,
emergency stop button |
|
Dimension
|
650*1000*1640mm(W*D*H)
|
|
Ambient Temperature
|
-10℃~+50℃
|
|
Mobility
|
Four wheels, lifting rings in chassis top
|
|
Humidity
|
≤95%
|
|
Altitude
|
≤2500 meters
|