This series of water meters is an instrument for measuring the total volume of water flowing through the pipe of tap water and is suitable for one-way flow. This series of water meter has the characteristics of advanced structure, accurate measurement and long service life. The liquid seal counter is sealed in a special liquid and has a reliable pressure compensation . It has the advantages of wet water meters and dry water meters.
1.Selected high quality materials. ductile iron . Steady & reliable characteristics
2. Dry-dial or wet- dial for option
3.Multiple-jet
4.Magnetic drive
5.Vacuum sealed register.
The reading can be kept clear in long-term service.
6. Anti-magnetic construction
7.Measuring accuracy is up to class B of ISO4064 Standard.
8. Packing: carton
9 Universal use. Easy for interchange & maintenance
10 Sizes:15mm- 40 mm
Applicable standardGB/T 778.1.2.3-2007
DIMENSIONS AND WEIGHT
NOTES ON INSTALLATION AND USAGE
Model | Meter size | Length (L1) | Length (L) | Width (B) | Height (H) | Weight | Connecting Thread | |
(mm) | KG | D | d | |||||
LXSY-15 | 15 | 165 | 259 | 98 | 105 | 1.5 | G3/4B | R1/2 |
LXSY-20 | 20 | 195 | 299 | 98 | 108 | 1.8 | G1B | R3/4 |
LXSY-25 | 25 | 225 | 339 | 103 | 118 | 2.4 | G1-1/4B | R1 |
LXSY-32 | 32 | 230 | 348 | 103 | 118 | 2.7 | G1-1/2B | R1-1/2 |
LXSY-40 | 40 | 245 | 379 | 128 | 157 | 4.5 | G2B | R2 |
1. It is suggested that the type and caliber of water meter should be determined according to the working conditions of water supply facilities , and the expected flow rate should be adapted to the flow rate of Q1 to Q3 of water meter
2. when the water meter is installing and start to be used, the upstream valve should be opened slowly to avoid hammer phenomenon caused by rapid opening, resulting serious damage to the water meter
3. Installation location should avoid exposure, freezing, flooding , keeping convenient to reading and installation and detach. during the freezing period, it is should keep the inlet valve of the water meter is closed when the water meter and the water pipe are wrapped, and keep the water outlet valve and faucet are opened to prevent the water meter being damaged by the expansion of freezing
4. the meter must be installed horizontally, keep the litera l upward, the direction of the arrow on the meter case should be as same as the water flow . to insure the accuracy of measurements the st rai ght pipe with enough length and the same perturb should be installed according to the requirement of U10 and D5. if necessary, a strainer can be installed between the upstream valve and the straight pipe, a non-return valve should be installed between the downstream straight pipe and the valve
5. All of the stones, mud, linen and other impurities must be cleaned out from the new pipeline before installation
6. the water meter should not be connected with the pipeline directly. there should be a live joint ( pipe joint, connecting nut, sealing gasket) between the water meter and the pipe. Care must be taken not to pull the meter too hard and damage it during assembling and removing process.
7. if the cold water meter is installed in the inlet pipe of the boiler, the hot water should be prevented to flow back and to scald the water meter