Summary
For installation at LPZ 0 B - 1 or higher , protecting 50 coaxial cable system, applied in coaxial system, cell sites and antenna system. This product is designed in accordance with IEC 61643.21/EN 61643-21/GB 18802.21.
Hightlight Features
• With exchangeable integrated gas discharge tube.
• High discharge capacity, low voltage protection level.
• Wide frequency range, high performance transmission.
• Metallic housing UHF ( M- F ) connection, easy for installation.
Application
B S G UHF is applied in various feed system, and so on.
Application environment
• Temperature: -40°C ~ +80°C
• Relative humidity: ≤ 95% (25°C)
Technical data
Type |
BS G UHF (M-F) (R eplacement gas discharge tube ) |
Rated voltage (max. continuous d.c. voltage) [Uc] |
90 V or 250V |
Nominal current [ I L ] |
3.5A |
Lightning impulse current ( 10 / 35 0) [ I imp ] |
1 kA |
Nominal discharge current (8/20) [ In ] |
10 kA |
Max. nominal discharge current (8/20) [ I max ] |
20kA |
Voltage protection level at In [ Up ] |
≤ 700 V |
Transmission frequency [ fG ] |
0- 3 GHz |
Max. output power [ P ] |
500W |
Insertion loss [ aE ] |
≤ 0. 2dB |
Return loss [ aR ] |
≥ 18 dB |
Characteristic impedance [ Z ] |
50Ohm |
C onnection input/output |
UHF (M-F) socket/plug |
Operating temperature range [ Tu ] |
-40°C...+80°C |
Earthing via |
O utgoing connecting port |
Dimension |
2 5 x 2 5 x 60 (mm) |
Test standards |
IEC 61643- 2 1; EN 61643-21; GB 18802. 2 1 |
Certification |
CE (LVD/EMC) , Ro HS |
Ordering information |
|
Type |
B S G UHF |
Art.-No. |
680 0 05 |
Packing unit |
1pc(s) |